9. Robot Configuration
242 EPSON RC+ 5.0 (Ver.5.4) User's Guide Rev.4
9.2 Calibrating the Robot
EPSON RC+ 5.0 provides a calibration wizard for calculating the robot calibration
parameters Hofs and Calpls.
To calibrate the robot:
1. From the Setup Menu, select Controller.
2. Click on the Robot folder in the tree on the left side to open the Robot Calibration page.
3. Select the joint to calibrate.
4. Click the Calibrate button to start the calibration wizard. The instructions for each
step are shown on the right side of the dialog.
5. Click the Jog button to jog the robot to the approximate zero pulse position, as shown
in the picture.
6. Click the Next button to view the next step.